On-Line UPS AHA-H 603H/104H/3104H/3204H LCD
Features
- Multiple Microprocessor design base
- Detachable control panel with LCD
- Unity input power factor and wide input range
- Robust design with output transformer
- True sine-wave double conversion on-line UPS
- DC start and automatic self-diagnostic function
- Capacity of battery unlimited and alarm silent
- RS232 communication port and built-in SNMP slot
- High efficiency design to save electricity
- Low heat dissipation in long term operation
- Designed to operate under harsh environment
- Enhanced protections against lighting surges, disturbances etc..
Overview
The Vesta series provides comprehensive protection and high power density in small and economic package. Compared to traditional UPS towers of the same size, Vesta UPS is more compact and offers greater comprehensive power protection against surges and spikes. Equipped with a voltage stabilizer, this UPS will continue providing clean and stable power to connected equipment while its embedded microprocessor controller guarantees high reliability, perfect for any home or small office applicatio
|
Model (LCD Series) |
AHA-603H |
AHA-104H |
AHA-3104H |
AHA-3154H |
AHA-3204H |
Input |
Capacity |
6KVA/4200W |
10KVA/7000W |
15kVA/10500W |
20kVA/14000W |
Phase |
Single Phase |
3 Phase |
Nominal Voltage |
1P2W 220Vac |
3P4W 380Vac |
Voltage Range |
176-276Vac 3Vac |
304-478 VAC |
Frequency |
50Hz / 60Hz 4Hz |
Power Factor |
0.98 |
0.95 |
Output |
Voltage |
220VAC 1% (230V or 240V re-settable via LCD panel) |
Frequency |
Synchronized ( Line mode); 50Hz or 60Hz +/-0.5% (Battery mode) |
Wave-form |
True Sine wave |
Distortion |
Tower |
4% (linear load)
7% non-linear load) |
Rack |
4% (linear load) , 7% non-linear load) |
N/A |
Overload Capacity |
108%~130%: 10mins , UPS go Bypass .
> 130% : 1 sec , UPS go Bypass ; 1 min, UPS shutdown. |
Crest Ratio |
3: 1 |
Battery |
DC Voltage |
240V |
Capacity |
12V/ 7Ah X 20pcs |
12V/ 9Ah X 20pcs |
Depend on the capacity of external batteries |
Back-up Time |
8 min. |
5 min. |
Depend on the capacity of external batteries |
Charger |
Built-In /Option |
2Amp/4.2Amp (2 steps) |
2Amp/4.2Amp (2 steps) |
Recharging Time |
7 hrs to 90% |
8 hrs to 90% |
Depend on the capacity of external batteries |
Bypass |
Automatic |
Overload or UPS fault |
|
By setting |
NA |
Transfer Time |
0 ms (AC to DC & inverter to bypass) |
Indicator |
LCD (Series) |
UPS status, I/P&O/P Voltage & Frequency ,Load %, Battery Voltage, Battery Capacity % ,Temperature, Model Spec., Event Log.
LED: Normal (Green), Warning (Yellow), Fault (Red) |
LED (Series) |
Normal (Green), Bypass(Yellow), Battery Low (Yellow), Inverter (Green), Load% (5 LEDs), Battery % (5 LEDs), Fault(Red) |
Outlet |
Tower |
Terminal Blocks |
Rack |
Terminal Blocks |
Audible
Alarm |
Battery Mode |
Beeping every 4 seconds (re-settable) |
Battery Low |
Beeping every seconds |
Overload |
Beeping twice per second |
Fault |
Beeping Continuously |
Interface |
RS-232 Interface |
UPSilon2000 monitoring software for Windows all, Unix systems and Novell. |
Multi-Interface Slot |
SNMP card, AS 400, Dry Contact, USB Selectable |
Network |
Surge Protection |
N/A |
Parallel |
Available (Option) |
Environment |
Temperature |
0~40J; 32~104K |
Humidity |
0-95% non-condensing |
Acoustic Noise |
55 dBA (at 1 M) |
60 dBA (at 1 M) |
Physical |
Weight (w/o Battery |
35 kgs |
38kgs |
38.5kgs |
55kgs |
55kgs |
Weight (w/ Battery) |
90 kgs |
93kgs |
--- |
--- |
--- |
Dimension W*H*D |
Tower |
260 x 717 x 570mm |
Rack |
482.6 x 176 (4U) x 600mm (Rack) |
NA |
Color |
White or Black |
*Tower Series: AHA-H, Rack Series: AHA-HR
*Rack Battery Bank (2U) is available for 8pcs (1 set) 12V/7Ah and 9pcs (3 sets) 12V/7Ah batteries.
*Specifications are subject to change without notice.
|
|